Heating Data Input: 50,000 BTUH max. Output: 40,000 BTUH Manifold Pressure: 3.5 in. w.c. Gas Supply Line Pressure: 10.5 in. w.c. max. / 4.5 in. w.c. min. Max. Outlet Air Temp.: 160 F Temperature Rise From: 30 - 60 F Max. Static Pressure: 0.5 in w.c. for altitudes to 0 - 4500 ft. Manufacturer Recommended Orifice Size: 1.75 mm Cooling Data Nominal Cooling Capacity: 7.0 kw (2 tons) Refrigerant: HCFC-22 Factory Charge: 3 lb-3 oz Min. Design Pressure: 278 psig High / 144 psig Low Electrical Rating: Operation: 208/230 V, 1-ph Min. Circuit Ampacity: 16 A Max. Fuse or Circuit Breaker: 25 A Motor Ratings Compressor each: 10.1 RLA, 1-ph, 60 LRA Indoor Blower Motor: 1/3 hp, 1-ph, 2.2 FLA Condenser Fan each: 1/6 hp, 1-ph, 1.1 FLA Combustion Air Blower: 208/230 V, 1-ph, 0.7 FLA |